Fuel gas boiler room electrical explosion-proof design abstract: Through the analysis fuel gas boiler room accident cause factor, as well as to the standard the understanding analysis, has carried on the explicit elaboration to the boiler room electricity explosion-proof design. Key word: Fuel gas; Boiler room; Explosion-proof; Flammable gas density examination foreword Because the fuel gas boiler room superiority and so on its inherent environmental protection are promoting, especially is producing is mad the rich area, massive newly built and the transformation fuel gas boiler room project starts in abundance. However the electrical explosion-proof part explicit design article, the regional designers have not known and the procedure are different, the following elaborated that to the standard the understanding, the difficult dispute question which and the solution in the exchange discussion design practice exists, refers for the fellow colleagues. 1 explosion hazard regionalism acts according to GB code "Boiler room Design Standard" GB50041-1992, in electrical part 13.2.2nd: The fuel oil accent presses, between the fuel oil pump house, the powdered coal preparation, the coal breaker and transports the coal corridor and so on to have detonation and the fire risk place rank division, must conform to the present national standards "Detonation And Fire risk Environment Power installation Design Standard" concerned requirements. Xinjiang Korla area natural gas relative density: 0.8, refer to "Detonation And Fire risk Environment Power installation Design Standard" GB50058-1992, the 2.3.1st note 2: The relative density is bigger than 0.75 fire damp stipulation for again in the air gas; Refers to the 2.3.4th explosion hazard regionalism, in seals up in the building to ventilate the bad process units area, [possibly namely the boiler room, the measurement and has in the room which the natural air line passes in and out is 1 area refers to when normal operation presents fire damp mixture environment]. According to "Architectural design Fire protection Standard" GB50016-2006, 3.1.1st, the boiler room is takes the fuel using the natural gas, carries on production which the combustion makes other to use, belongs to the Ding kind of production fire hazard, simultaneously rests on the 3.1.1st 4 article explanation②, “Ding kind” the 2nd item: Although using the gas, the fuel or the solid carries on the combustion for the fuel, is the open fire production, but in the fixed equipment internal combustion, is not easy to create the fire. Although also has some explosion accident, but belongs to the physical property to explode generally, like boiler room, lime-roasting, blast furnace workshop and so on production. The above two standard contrasts see, the open fire production's boiler room, in the actual movement, divided into 1 area already not to have the too big significance. However, now in the enterprise, for instance the oil gas production pursue essence security, is through pursues in its flow the human, the thing, the system, the system and so on various essential factor security reliable harmonious unification, causes each kind of harm factor to be at throughout the control state, then draws close gradually the essence, the permanent security goal. How then to carry on the electrical design? 2 accident cause factors analyze the fuel gas boiler room accident's reason, has two kind of possibilities: The boiler proper explodes, the boiler room fire damp to achieve the explosion ratio to have the detonation. The boiler proper explodes, is because has the explosivity gaseous mixture existence in the chamber or the flue, when achieves the explosive limit, creates the accident by the open fire or boiler's high temperature ignition. This point is related the article showing match case with "Architectural design Fire protection Standard". The actual present boiler product had already considered the safety in production measure avoids. The qualified gas-fired boiler itself has the explosion-proof technological design, like the burner in the unusual circumstance auto-stop, the automatic control installment also stops the output fuel; The gas-fired boiler combustion system automaticity was high, includes the fuel gas pressure to be high, lower limit warning protection and so on, when controlled which step logical judgement didn't satisfy the hypothesis condition, start corresponding interconnection protection. Avoided the boiler proper exploding the possibility, but still had the above other one kind of possibility, whether to avoid? How to avoid?