随着国家经济水平的不断提高,钢结构房屋越来越多,广泛应用于工业和民用建筑中。下面是我整理钢结构设计经验的范文,欢迎阅读!
钢结构设计经验篇一
1.设计时钢材、焊缝质量等级的正确选用
在钢结构设计文件中,应当注明所用钢材的质量等级(包括相适应的焊接材料型号),并对焊缝质量提出质量等级要求。钢结构房屋所使用的钢材应当具有抗拉强度、屈服强度、伸长率、冷弯试验和硫、磷含量的合格保证;对于焊接钢结构,尚应具有含碳量的合格保证。在地震区,钢结构所使用的钢材,除了具有上述合格保证外,《建筑抗震设计规范》(gb5001l-2001)还要求它们具有冲击韧性的合格保证。为保证结构有必要的安全储备和足够的塑性变形能力,《建筑抗震设计规范》(gb5001l-2001)还对钢材的抗拉强度实测值与屈服强度实测值的比值、伸长率的限值和良好的可焊性等物理力学指标做出了明确的规定,并要求写入设计文件中。通常,钢结构的主要受力构件宜采用q235b 及以上等级的碳素结构钢和q345b 及以上等级的低合金高强度结构钢。不建议使用质量等级为a 级的钢材,原因是这种类型的钢材不保证冲击韧性和延性性能,q235a级钢材还不保证焊接要求的含碳量限值。在钢结构中,焊接连接已成为钢结构连接的最基本方法,焊缝质量的好坏直接影响到结构安全,所以应当根据结构或构件的重要性和受力性能及焊缝的受力情况,确定焊缝的质量等级。一般来说,板材的对接焊缝,承受动力荷载构件(如吊车梁)的较重要的焊缝,需作疲劳验算的焊缝,以及须与钢材等强的受拉、受弯对接焊缝(如框架梁、柱及其连接节点的对接焊缝,工字形截面与其端板的对接焊缝),其焊缝应采用坡口全熔透对接焊缝,其焊缝质量等级不得低于二级。其他部位的焊缝,一般均可采用角焊缝。角焊缝由于应力集中现象严重,内部探伤亦很困难.其焊缝质量等级一般只能是三级,其中某些重要角焊缝可允许要求其外观缺陷符合二级的要求。
2.门式钢架房屋的温度区段内应按规范设置独立的空间稳定支撑体系
(1)应将屋面横向水平支撑和柱间支撑布置在同一跨间内,形成独立的空间支撑体系,既利于抗震,又给施工安装带来方便。
(2)将屋面横向水平支撑设在端部第二个开间的同时,应在端跨相应位置设置刚性纵向系杆,使山墙的风荷载等水平力能可靠传递。
(3)屋面支撑的布置应与山墙抗风柱的位置相协调,使抗风柱的柱顶反力能直接传到屋面横向支撑的节点上,使山墙处屋面系统受力简单化,从而保证结构的安全。
(4)屋面横向水平支撑的直腹杆(包括屋脊处和柱顶处)应按刚性系杆考虑。采用檩条兼做时,应对檩条的刚度和承载力进行验算。否则,檩条很难起到刚性系杆作用,因为常用的z 形或c 形冷弯薄擘型钢檩条侧向刚度很差,直接影响到房屋的纵向受力和传力性能。当檩条无法起到刚性直腹杆的作用时,通常应在屋脊处、柱顶处以及屋面设置横向水平支撑直腹杆,在刚架斜梁间设置钢管、h 型钢或其它截面形式的刚性杆件,以保证房屋纵向结构安全可靠地工作。在刚架转角处(边柱柱顶和屋脊,以及多跨房屋相应位置的中间柱柱顶)的刚性系杆应沿房屋全长设置。
(5)屋面支撑和柱间支撑当采用柔性圆钢拉条时,宜设张紧装置(如花兰螺栓),当荷载较大时,柔性圆钢拉条宜改为型钢。
3.实腹式门式刚架应按规范设置隅撑
在檩条或墙梁与刚架的连接处,在斜梁下翼缘的受压区或刚架柱内侧翼缘的受压区,至少每隔一根檩条或墙梁应设置按受压构件设计的隅撑,将檩条或墙梁与翼缘受压区直接连接起来。采用双层屋面板时亦应设置隅撑。值得设计人员注意的是,隅撑虽小,但作用很大,它是用来保证斜梁下翼缘或刚架柱内侧翼缘受压稳定的重要措施。如果工程未按规范要求设置隅撑,或者设置得很少,或者设置得不当.这都将影响刚架的整体稳定性,危及结构的安全。
4.压型钢板轻型屋面拉条的合理设置
对于有檩体系的压型钢板轻型屋面,为了减少檩条在使用阶段和施工过程中的侧向变形和扭转,通常在檩条间要设置拉条和撑杆作为檩条的侧向支点,以保证檩条的侧向稳定。拉条按拉杆设计,撑杆按压杆设计。拉条和撑杆不大,但作用不小,设计人员必须十分重视。
5.楼面结构设计
(1)钢结构房屋和混凝土结构房屋由于材料性质不同。温度伸缩缝区段长度差别很大。例如现浇混凝土框架结构房屋。温度伸缩缝区段长度最大为55m,钢框架结构房屋。温度伸缩缝区段长度约为120mm。为了防止或减轻混凝土楼板开裂.钢框架结构房屋采用现浇混凝土楼板时,原则上仍应按混凝土结构的要求留设温度伸缩缝。只有当采用设置施工后浇带和其它减小混凝土温度变化或收缩的可靠措施时,才可以适当增大温度伸缩缝区段长度。
(2)压型钢板组合混凝土楼板,除了按计算(并满足构造要求)在钢梁上焊接栓钉外,为了保证混凝土和压型钢板共同工作,它们之间应有连接措施。其连接措施可以依靠压型钢板的纵向波槽或依靠压型钢板上的压痕、开的小洞或冲成的不闭合孔眼,也可以依靠压型钢板上焊接的横向钢筋。由于产品规格的限制,目前国内带纵向波槽的压型钢板和带压痕或开小洞的压型钢板不多。所以,当无法采用上述这两种板型时,要实现压型钢板和混凝土的连接,可在压型钢板上焊接横向钢筋。
钢结构设计经验篇二
一、轻型厂房: 这里主要指门式钢架,通常我们能做到的跨度大概就是15-36米的样子,其实做到36米的时候用钢量已经不小,基础也比较大(钢架比较小(如24米以内)的时候柱底铰接,比较大的时候用刚接)。当然,即使9米跨度,也可以做成钢架,而且这种情况还不少,主要用于不能打支撑又需要承受水平力的情况。其实门刚很简单,可以说是最简单的钢结构,因为有标准图集。这里我简单说一下;门刚的组成--门刚(骨架),檩条,系杆,支撑,墙檩,抗风柱。基本上就这几样,下面一一说明。门刚,可用pkpm或者其它软件建模计算,导入荷载即可,恒载就是自重(檩条,支撑,屋面压型钢板及保温层等),活荷载按荷载及门刚规范取即可(地震荷载通常不起控制作用)。这里要注意一点,门刚要注意尽量用较薄的杆件,这里是采用屈曲后的强度,在需要的时候设置构造加劲肋。其实这些书上都有的。通常屋面非轻钢专业户设计的这种门刚,30米跨以内的,应该控制用钢量在30kg左右。檩条,门刚图集上都有,根据荷载选取即可。檩条之间构造连接教科书或者图集上均有,通常选用C型或者Z型檩条(Z型檩条有个好处是可方便连接,并将檩条做成连续跨)。然后是系杆,系杆这个东西很重要,就是保证整体稳定的,保证整体稳定其实非常简单,就是每隔一段距离,我们要做一个稳定的结构,其它跨通过系杆与这一跨稳定的东东连接在一起就可以了,所以这一跨稳定的结构,我们要设置柱间支撑,同时要设置屋面支撑(还有一种轻钢就是采用桁架式,这个时候需要设置上下弦支撑),以保证这一跨的静定结构。下面说支撑,其实上一条已经说明,就是那几招。墙檩:基本上同屋面檩条,由风荷载控制,抗风柱,按下端固结,上端铰接计算,其实是类似于梁来考虑的(pkpm中有专门计算抗风柱的一个工具),这里注意一点即可,如果选用桁架式图集,这个时候抗风柱一定要同时跟上下弦连接,并在布置的时候考虑对齐(与桁架节点对齐)。
二,多层钢结构(包括钢平台) 这种东西其实也比较简单,就是一个梁柱的连接过程,无非就是考虑一下梁柱的大小,其实主要是梁,通常情况,对于H或者工字钢,对于9米以内的梁,一般荷载(活荷载4以内),梁高可以取到跨度的1/30,对于槽钢,可以1/25,对于柱子,通常情况用长细比控制,保证弱轴方向在100以内一般验算均可满足。对于国内普通厂房,通常采用设置支撑的方式来进行设计,因为这样一来简单,而来经济(梁柱其实可以采用刚性节点,但不光是节点费力费钱,整体计算的时候也要复杂-费材料一些),当然,很多情况还是需要做成刚节点。但,通常如果设置了支撑以后,结构可按无侧移计算,(国内采用pkpm稍微麻烦一点,因为pkpm不能单侧选择无侧移或者有侧移,只能整体)相对来说很多指标均很好控制。另外,钢结构楼面一般选用花纹钢板或者格栅板,从刚度上来说,格栅板有优势,但格栅板上面走动肯定会掉灰下来。 其实钢结构设计,说到底长细比是一个很重要的概念,拉杆,压杆,都不一样。通过长细比的概率,再计算应力及稳定,重点其实是稳定。然后就ok了 总结:钢结构最重要的是支持体系,即保证稳定,所以,我们通常做成超静定体系,这样发生问题以后不至于倒塌。特别说明,钢结构虽然也可以悬挑,但通常我们都要增加支撑,特别是高层,主要是保证其为超静定体系。
钢结构设计经验篇三
(一) 判断结构是否适合用钢结构
钢结构通常用于高层、大跨度、体型复杂、荷载或吊车起重量大、有较大振动、要求能活动或经常装拆的结构。直观的说:大厦、体育馆、歌剧院、大桥、电视塔、雕塑、仓棚、工厂、住宅、山地建筑和临时建筑等。这是和钢结构自身的特点相一致的。
(二) 结构选型与结构布置
结构选型及布置是对结构的定性,由于其涉及广泛,应该在经验丰富的工程师指导下进行。此处仅简单介绍. 详请参考相关专业书籍.
在钢结构设计的整个过程中都应该被强调的是"概念设计",它在结构选型与布置阶段尤其重要. 对一些难以作出精确理性分析或规范未规定的问题,可依据从整体结构体系与分体系之间的力学关系、破坏机理、震害、试验现象和工程经验所获得的设计思想,从全局的角度来确定控制结构的布置及细部构造措施。 在早期迅速、有效地进行构思、比较与选择,所得结构方案往往易于手算、力学行为清晰、定性正确,并可避免结构分析阶段不必要的繁琐运算。同时,它也是判断计算机内力分析输出数据可靠与否的主要依据。
林同炎教授在《结构概念和体系》一书中介绍了用整体概念来规划结构方案的方法,以及结构总体系和个分体系间的相互力学关系和简化近似设计方法。
钢结构通常有框架、平面桁架、网架(壳)、索膜、轻钢、塔桅等结构形式。
其理论与技术大都成熟。亦有部分难题没有解决,或没有简单实用的设计方法,比如网壳的稳定等。
结构选型时,应考虑不同结构形式的特点。在工业厂房中,当有较大悬挂荷载或大范围移动荷载,就可考虑放弃门式刚架而采用网架。基本雪压大的地区,屋面曲线应有利于积雪滑落(切线50度外不需考虑雪载 ),如亚东水泥厂石灰石仓棚采用三心圆网壳,总雪载和坡屋面相比释放近一半。降雨量大的地区相似考虑。建筑允许时,在框架中布置支撑会比简单的节点刚接的框架有更好的经济性。而屋面覆盖跨度较大的建筑中,可选择构件受拉为主的悬索或索膜结构体系。高层钢结构设计中,常采用钢混凝土组合结构,在地震烈度高或很不规则的高层中,不应单纯为了经济去选择不利抗震的核心筒加外框的形式。宜选择周边巨型SRC柱,核心为支撑框架的结构体系。我国半数以上的此类高层为前者,对抗震不利。 结构的布置要根据体系特征,荷载分布情况及性质等综合考虑.一般的说要刚度均匀.力学模型清晰.尽可能限制大荷载或移动荷载的影响范围,使其以最直接的线路传递到基础. 柱间抗侧支撑的分布应均匀.其形心要尽量靠近侧向力(风、震)的作用线. 否则应考虑结构的扭转. 结构的抗侧应有多道防线. 比如有支撑框架结构,柱子至少应能单独承受1/4的总水平力. 框架结构的楼层平面次梁的布置,有时可以调整其荷载传递方向以满足不同的要求。通常为了减小截面沿短向布置次梁,但是这会使主梁截面加大,减少了楼层净高,顶层边柱也有时会吃不消,此时把次梁支撑在较短的主梁上可以牺牲次梁保住主梁和柱子.
(三) 预估截面
结构布置结束后,需对构件截面作初步估算。主要是梁柱和支撑等的断面形状与尺寸的假定。
钢梁可选择槽钢、轧制或焊接H型钢截面等。根据荷载与支座情况,其截面高度通常在跨度的1/20~1/50之间选择。翼缘宽度根据梁间侧向支撑的间距按l/b限值确定时,可回避钢梁的整体稳定的复杂计算,这种方法很受欢迎。 确定了截面高度和翼缘宽度后,其板件厚度可按规范中局部稳定的构造规定预估。
柱截面按长细比预估. 通常50<λ<150, 简单选择值在80附近。根据轴心受压、双向受弯或单向受弯的不同,可选择钢管或H型钢截面等.
对应不同的结构,规范对截面的构造要求有很大的不同,如钢结构所特有的组成构件的板件的局部稳定问题,在普钢规范和轻钢规范中的限值有很大的区别。
除此之外,构件截面形式的选择没有固定的要求,结构工程师应该根据构件的受力情况,合理的选择安全经济美观的截面。
(四) 结构分析
目前钢结构实际设计中,结构分析通常为线弹性分析,条件允许时考虑P-Δ,p-δ.
新近的一些有限元软件可以部分考虑几何非线性及钢材的弹塑性能.这为更精确的分析结构提供了条件。并不是所有的结构都需要使用软件:
典型结构可查力学手册之类的工具书直接获得内力和变形.
简单结构通过手算进行分析.
复杂结构才需要建模运行程序并做详细的结构分析.
(五) 工程判定
要正确使用结构软件,还应对其输出结果的做"工程判定"。比如,评估各向周期、总剪力、变形特征等。根据"工程判定"选择修改模型重新分析,还是修正计算结果.
不同的软件会有不同的适用条件.初学者应充分明了.此外,工程设计中的计算和精确的力学计算本身常有一定距离, 为了获得实用的设计方法,有时会用误差较大的假定, 但对这种误差, 会通过"适用条件、概念及构造"的方式来保证结构的安全. 钢结构设计中,"适用条件、概念及构造"是比定量计算更重要的内容.
工程师们过分信任与依赖结构软件有可能带来结构灾难,注重概念设计、工程判定和构造措施有助于避免这种灾难.
(六) 构件设计
构件设计首先是材料的选择. 比较常用的是Q235和Q345. 当强度起控制作用时,可选择Q345; 稳定控制时,宜使用Q235.通常主结构使用单一钢种以便于工程管理. 经济考虑,也可以选择不同强度钢材的焊接组合截面(翼缘Q345,腹板Q235). 另外,焊接结构宜选择Q235B或Q345B。
当前的结构软件,都提供截面验算的后处理功能。部分软件可以将不通过的构件,从给定的截面库里选择加大一级自动重新验算,直至通过,如sap2000等。这是常说的截面优化设计功能之一,它减少了很多工作量。 但是,我们至少应注意两点:
1.软件在做构件(主要是柱)的截面验算时,计算长度系数的取定有时会不符合规范的规定.目前所有的程序都不能完全解决这个问题。所以,尤其对于节点连接情况复杂或变截面的构件,我们应该逐个检查.
2.当上面第(三)条中预估的截面不满足时,加大截面应该分两种情况区别对待。
(1) 强度不满足,通常加大组成截面的板件厚度,其中,抗弯不满足加大翼缘厚度,抗剪不满足加大腹板厚度。
(2) 变形超限,通常不应加大板件厚度而应考虑加大截面的高度,否则会很不经济。 使用软件的前述自动加大截面的优化设计功能,很难考虑上述强度与刚度的区分,实际上,除常用于网架设计外,其他结构形式常常并不合适。
(七) 节点设计
连接节点的设计是钢结构设计中重要的内容之一.在结构分析前,就应该对节点的形式有充分思考与确定.有时出现的一种情况是,最终设计的节点与结构分析模型中使用的形式不完全一致,如果你不能确信这种不一致带来的偏差差在工程许可范围内(5%),就必须避免。 按传力特性不同,节点分刚接,铰接和半刚接. 初学者宜选择可以简单定量分析的前两者.常用的参考书有丰富的推荐的节点做法及计算公式.
连接的不同对结构影响甚大.比如,有的刚接节点虽然承受弯矩没有问题,但会产生较大转动, 不符合结构分析中的假定. 会导致实际工程变形大于计算数据等的不利结果.
连接节点有等强设计和实际受力设计两种常用的方法, 初学者可偏安全选用前者.设计手册[2]中通常有焊缝及螺栓连接的表格等供设计者查用,比较方便. 也可以使用结构软件的后处理部分来自动完成.
具体设计主要包括以下内容:
1.焊接: 对焊接焊缝的尺寸及形式等,规范有强制规定,应严格遵守. 焊条的选用应和被连接金属材质适应.E43对应Q235,E50对应Q345. Q235与Q345连接时,应该选择低强度的E43,而不是E50.
焊接设计中不得任意加大焊缝. 焊缝的重心应尽量与被连接构件重心接近.其他详细内容可查规范关于焊缝构造方面的规定.
2.栓接:
铆接形式,在建筑工程中,现已很少采用.
普通螺栓抗剪性能差, 可在次要结构部位使用.
高强螺栓,使用日益广泛.常用和两个强度等级.根据受力特点分承压型和摩擦型.两者计算方法不同. 高强螺栓最小规格M12. 常用M16~M30. 超大规格的螺栓性能不稳定,应慎重使用。
自攻螺丝用于板材与薄壁型钢间的次要连接. 在低层墙板式住宅中也常用于主结构的连接. 难以解决的是自攻过程中防腐层的破坏问题。
3.连接板: 需验算栓孔削弱处的净截面抗剪等. 连接板厚度可简单取为梁腹板厚度加4mm,则除短梁或有较大集中荷载的梁外,常不需验算抗剪。
4.梁腹板: 应验算栓孔处腹板的净截面抗剪.承压型高强螺栓连接还需验算孔壁局部承压.
5.节点设计必须考虑安装螺栓、现场焊接等的施工空间及构件吊装顺序等。构件运到现场无法安装是初学者长犯的错误。此外,还应尽可能使工人能方便的进行现场定位与临时固定。
6.节点设计还应考虑制造厂的工艺水平. 比如钢管连接节点的相贯线的切口可能需要数控机床等设备才能完成.
(八) 图纸编制
钢结构设计出图分设计图和施工详图两阶段,设计图由设计单位提供,施工详图通常由钢结构制造公司根据设计图编制,有时也会由设计单位代为编制。由于近年钢结构项目增多和设计院钢结构工程师缺乏的矛盾,有设计能力的钢结构公司参与设计图编制的情况也很普遍。
1.设计图: 是提供制造厂编制施工详图的依据. 深度及内容应完整但不冗余. 在设计图中,对于设计依据、荷载资料(包括地震作用)、技术数据、材料选用及材质要求、设计要求(包括制造和安装、焊缝质量检验的等级、涂装及运输等)、结构布置、构件截面选用以及结构的主要节点构造等均应表示清楚,以利于施工详图的顺利编制,并能正确体现设计的意图。主要材料应列表表示。
2.施工详图:又称加工图或放样图等.深度须能满足车间直接制造加工.不完全相同的另构件单元须单独绘制表达,并应附有详尽的材料表.
设计图及施工详图的内容表达方法及出图深度的控制,目前比较混乱,各个设计单位
之间及其与钢结构公司之间不尽相同。 初学者可参考他人的优秀设计并参考相关的工具书,并依据规范规定编制。
概念设计的一个方面:
当你在设计中,能够把结构看作构件,把构件看作结构,你就已经走近概念设计了。
把结构当作构件,比如,一栋大厦的结构就是一根悬臂梁, 一座桁架大铁桥就是一根连续梁。
把构件看作结构,比如,一个H型钢构件是由3块板组成的结构,一个钢管相贯的节点就是一个空间结构。
对构件特性的把握:
比如,钢管适合做二力(压)杆,不适合做抗弯构件。它做两端铰接柱或支撑很出色,但是很少用作梁。 当一个受弯构件被选成钢管截面,且程序计算不通过时,你不应通过加大截面来满足,而是应该改用有强弱轴的截面。
如此等等,是基本的概念。
概念设计能力,不单生成于丰富的经历与经验,更是来源于对基本的力学、材料等概念掌握。同时要求结构师有开阔的视野。
关于钢结构在建筑结构设计中存在的问题分析论文
1钢结构设计概述
随着建筑施工工艺的提升,刚性结构建筑施工逐渐取代混凝土施工建设,为了保证钢结构施工建设的质量,拓宽了钢结构的施工建设领域。
结构布置的依据
钢结构的设计应该从经济和物理两个角度进行判断:一方面,钢结构在施工建设过程中运用时一定要确保其经济成本比较低,能够容易让业主接受;另一方面;为了确保钢结构的设计质量和施工质量,要提升钢结构的物理承受能力,具体表现在结构布局上,这方面应该严格综合考虑其体系特征、荷载的性质以及分布情况。一般情况下要是力学模型清晰、刚度均匀,要尽量限制的影响范围是大荷载及其移动荷载等,使它把线路能够直接的传递到基础。尤其要注意的是,柱间抗侧支撑的一定要均匀分布,共形心要尽可能地向风震的作用线靠近,否则就必须考虑整体结构的扭转以及结构抗侧的多道防线。
结构分析和工程判定
当代建筑通过计算机软件系统的结构分析技术改变了传统的结构分析方法,提高了分析工作的工作效率,同时也提高了分析数据的高度准确性,然而我们应该意识到,鉴于工程在实际施工中会出现很多突发性状况,再加上其地质复杂,所以必须要结合相应的人工实地考察结果来分析软件,只有这样才能使结构分析更具有可操作性。
建筑钢结构的特点
钢结构之所以被广大施工单位所重视,之所以占据了建材市场巨大比例,主要是因为:首先,钢结构较为匀称。在一定应力的条件下,钢结构受力所产生的实际弹性与理想中的计算数据较为接近,材质和内部结构较为稳定。其次,钢材强度比一般的建材强度要高,而且其体积要小于一般的建材,建筑施工时可用面积较大。而且钢材内部结构排列精密,自身重量较轻,在遇到突发自然灾害时能够降低建筑物自重,同时降低整个工程的造价。最后,钢材不同于钢筋等材料,其具有较强的可塑性,不会出现因载重过量而发生折断的现象,这主要是因为钢材内部对应力平衡把握以及对外来作用力的合理分配。
2钢结构在建筑结构设计中的问题
设计质量下降
进行钢结构设计所需的人力和物力资源比一般的建筑方案设计要大得多,而且其设计时间期限一般较短,所给予的设计经费较少,设计任务量又较大,因此,钢结构设计任务经常出现无人接收问题,就算设计任务被接受,其设计质量也往往是差强人意。施工单位在承包一项工程后,往往会将这个工程的钢结构设计任务进行转包,因为施工单位很少有具备专业钢结构设计资格的,但是由于工程转包的设计单位可能也缺乏相应的经验和人才,此情况下往往会因为建筑市场的混乱而造成钢结构设计工作的失败。而且,由于缺乏相应的监督制度和法律规范文件,一般很难采取有效措施进行整治,这就造成钢结构设计质量普遍下滑的局面。
参与建设人员的素质相对不高
钢结构设计工作本身就是一项任务繁重的工作,而当前建筑钢结构设计行业又普遍存在设计人员专业素质缺乏的现象,这更加突出了钢结构设计的问题。除了设计人员的专业素质缺乏之外,施工单位往往也存在施工人员和高层管理人员缺乏专业素质和职业素养的现象。不论是什么工作,工作人员都是保证工作质量的关键所在,而钢结构设计工作更是如此。所以,建筑企业必须认识到这一问题的重要性,积极提高当前钢结构设计人员和施工人员以及高层管理人员的专业素质和职业素养。
对国外设计方案不加变通
我国钢结构设计工作相较于外国先进国家来说存在一定差距,因此,我国钢结构设计师经常在进行钢结构设计工作时借鉴外国的设计方案。当然,适当的借鉴是允许的,但是,我国大部分的设计人员对待外国设计方案都是推崇、照搬照抄,根本没有考虑设计方案的适用性,没有结合本国的实际情况进行修改,将其方案不加变通地挪用到我国钢结构设计工作中,造成建筑企业的.经济损失。还存在一些设计人员,不切实际,进行设计任务时,思维过于天马行空,根本不结合实际情况。
3钢结构在建筑结构设计中的改进措施
建筑钢结构设计的思路和步骤
为了能够使钢结构的设计更具有科学性,设计人员就应该严格按照既定的设计方案进行操作,而且要注意将不同环节的细节工作具体落实到位。
钢结构的形式与布置。钢结构主要有框架、平面架、网架、索膜、轻钢以及塔桅等结构形式。每个形式都有其各自的特点,工程在选型的时候应该结合具体的情况考虑它们的特点。钢结构的形式虽然比较多,但是其施工并没有固定的标准和规律供参照,因此,设计人员一定要对客观分析建筑施工的实际情况和周边环境,进而综合考量,最终确定最优方案。
图纸的编制。图纸是建筑施工的蓝本,所以为了确保钢结构施工建设的质量,设计工作人员必须运用科学的设计方法对图纸进行设计,同时要对图纸进行反复的操作性判断,组织专业素质好、工作经验丰富的设计团队进行全体的讨论,最终确定。
针对钢结构设计的合理化建议
钢结构设计对建筑工程质量而言有着决定性的作用,因此必须对钢结构设计工作进行严格的监督检测,健全相应的监督制度,加强制度执行力度。而若想做好对设计工作的监督和检测工作,就必须完善相应的管理制度,例如监督制度、检测制度以及对设计人员的奖惩制度等,只有用奖惩制度激励设计人员,用监督制度督促设计人员,用检测制度去保证设计方案的质量,才能保证钢结构设计的最终完工质量。而在这些管理制度制定和执行的过程中,可以借鉴相关的法律文件进行完善。
在进行设计工作时,无论是自己进行创新还是借鉴外国先进的设计方案作品,都要根据自己的实际情况来进行钢结构设计任务。只有保证建筑物结构的稳定性以及建筑的使用性能,这里的使用性能即建筑物的舒适性、健康性以及自由性,才能说明这个钢结构设计的成功。而且,在设计时要充分考虑到钢结构在建筑物内部的作用和载重性能,要遵循一般的规律和原则进行设计工作。
进行钢结构设计工作时不能只追求表面功能,要将其功能性深入化,提高其设计深度。要考虑建筑物所能遇到的多种环境状况,并根据这些环境状况来设计钢结构的使用性能,以此提高建筑物的使用年限。这样优质的钢结构设计成果还能够为设计单位树立品牌和提高信誉度。钢结构设计方案完成后,不能立刻投入施工中,要对其进行重重的审查,只有满足多重审核之后,充分保证了设计方案的合理、科学性之后,才能将设计方案正式投入施工,这样能够避免设计施工的风险。
4结语
综上所述,钢结构在建筑结构领域中担任着重要的角色,必须重视对钢结构的设计。在进行设计方案时要注意上述几个需要关注的重点,提高钢结构设计方案的质量,保证钢结构的稳定性和安全性,从而保证建筑物的结构质量。
钢结构的焊接技术的好坏,在一定程度上会影响到建筑本身的质量。下面我整理了钢结构焊接技术论文,欢迎大家阅读!钢结构焊接技术论文篇一:《钢结构安装焊接施工技术》 摘要:某工程塔楼为全钢结构,焊接工作量大,且大部分为全熔透焊缝,质量要求高,构件板厚最大达到85mm,焊接难度大。工程开始前进行了工艺评定。 关键词:钢结构;焊接;全熔透焊;工艺评定 1工程概况 某工程位于湖南长沙,为全钢结构,地上35层,钢柱锚入地下一层,高150m.南北立面为双曲面,外围钢柱以每4层为一折线点。核心筒共31根钢柱,外围钢框架柱共23根。钢柱主要为箱形柱,钢梁为轧制、焊接H形梁。钢结构总重量约14000t。 钢材 本工程钢柱使用的钢材为高层建筑结构用钢板Q345GJC,大于40mm厚钢板为Q345GJC-Z15,产地为舞阳钢铁厂,主梁使用钢材为Q345C,钢支撑采用Q235C,产地为武汉钢铁厂。 构件 钢柱长12m,构件单件最重,钢柱板厚28、34、40、55、70、85mm,典型截面600×600×70,钢梁翼缘板厚16、24、28、40mm,典型截面700×240×14×28。由于钢板厚度大,因此焊接难度大,焊接质量要求高。 节点形式与焊缝检测 按照设计,现场安装柱与柱之间的对接为全熔透焊,钢梁与钢柱牛腿上、下翼缘为全熔透焊,钢梁腹板大部分为高强螺栓连接,双剪连接板与钢柱为角焊缝。 由于钢板厚度大,焊缝又多数是全熔透焊缝,所以对本工程的全熔透焊缝实施B级超声波检测,100%超声波探伤。现场探伤工作中,由现场焊接员填写检测委托单,检测单位按照填写的检测部位进行探伤。如发现焊接缺陷,检测单位填写质量返修单,通知焊接负责人,进行返修重焊后,再进行超声波探伤。本工程委托单位为冶金院检测所,采用的仪器为CTS-2000,选用斜探头进行超声波探伤。探伤 报告 必须明确探伤部位、缺陷的位置和大小、评定级别,并判定合格或不合格;返修部位严格按照焊接工艺评定的参数进行焊接,返修不得超过二次。 2典型焊接节点概况 钢柱对接焊缝。 3焊接准备 焊接吊篮与平台 焊接设备和焊接材料 4焊接施工劳动力安排 高层钢结构焊接工程专业性很强,劳动强度大,专业管理人员和焊工都要求有较好的技术素质。本工程现场焊工均持有钢结构焊接CO2气体保护焊合格证,在正式施工前,在业主、监理等各单位的监督下进行了现场附加考试。 5焊接施工顺序和工艺 焊接顺序 根据本工程平面和立面形状,结构形式等,塔楼分东西两区组织施工。当钢结构安装完成三个及以上单元的校正和高强螺栓的终拧后,从平面中心选择四面都有焊接梁的柱子作为基准柱,并以此作为垂偏测量基准,并首先安排其四侧都有抗弯焊接的梁、然后向四周扩展施焊。随安装滞后跟进。采取结构对称、节点对称和全方位对称焊接的原则。 栓-焊混合节点中,设计要求梁的腹板上的高强度螺栓先初拧70%后→焊接梁的下、上翼缘板→终拧梁腹板上的高强度螺栓至100%施工扭矩值。 竖向上的焊接顺序: (1)地下一柱一层梁的焊接顺序: 上层框架梁→柱脚板部位的焊接→支撑→焊接检验。 (2)地上及以上一柱二层梁的焊接顺序: 上层框架梁→压型金属板支托→下层框架梁→压型金属板支托→上柱与下柱焊接→焊接检验(也可先焊柱—柱节点→上层框架梁→下层框架梁→焊接检验)。 (3)地上及以上一柱三层的焊接顺序: 上层框架梁→压型金属板支托→下层框架梁→压型金属板支托→中层框架梁→压型金属板支托→上柱与下柱焊接→焊接检验,(但也可先焊柱—柱节点→上层框架梁→下层框架梁→中层框架梁→焊接检验)。 柱—梁节点上对称的两根梁应同时施焊,而一根梁的两端不得同时施焊作业。 柱—柱节点焊接时,箱形柱的对称两面应由两名焊工相对依次逆时针焊接。 梁的焊接应先焊下翼缘,后焊上翼缘,以减少角变形。 安装焊接工艺 安装焊接前的准备工作 本工程使用的高层建筑结构用钢板在国内应用并不多,针对其中数量较多且具有代表性的接头形式进行了相应焊接 方法 的工艺评定试验。试验钢材包括Q345GJC-Z15(壁厚70mm)、Q345GJC-Z15(壁厚40mm)、Q345C(翼缘厚28mm),焊接位置为柱—柱横焊、柱—梁平焊(包括桁架梁上下翼缘平焊)、T型角立焊。坡口形式及尺寸按设计要求。焊后外观及超声波检查合格后取样进行了力学和物理试验。试验结果接头的抗拉强度达到母材抗拉强度标准值,接头弯曲180°无裂纹。采用的焊接材料和焊接设备技术条件应符合国家标准,性能优良。清渣、气刨、焊条烘干保温等装置应齐全有效。 手工电弧焊及CO2气保焊焊材和设备 (1)焊条应在高温烘干箱中150℃烘干2小时,且焊条烘干次数不得超过两次。 (2)焊丝包装应完好,如有破损而导致焊丝污染或弯折、紊乱时应部分弃之。 (3)CO2气体纯度应不低于(体积比),含水量应低于(重量比),瓶内高压低于1MPa时应停止使用。 (4)焊机电压应正常,地线压紧牢固,接触可靠,电缆及焊钳无破损,送丝机应能均匀送丝,气管应无漏气或堵塞。 安装焊接程序及一般规定 焊接的一般顺序为:焊前(装配)检查→装焊垫板和引弧板→除锈预热→焊接→检验(返修,不得超过二次), 焊前检查坡口角度、钝边、间隙及错边量(小于规范要求),坡口内和两侧的锈斑、油污、氧化铁皮等应清除干净。 装焊垫板及引弧板,其表面清洁程度要求与坡口表 面相 同,垫板与母材应贴紧,引弧板与母材焊接应牢固。 预热。焊前用气焊或特制烤枪对坡口及其两侧各100mm范围内的母材均匀加热,并用表面测温计测量温度,防止温度不符合要求或表面局部氧化,预热温度。 钢结构焊接技术论文篇二:《钢结构的安装焊接施工技术》 摘要:本文简要分析了厂房钢结构焊接施工的主要工艺及保障焊接质量的主要方法,并提出了控制焊接质量的主要对策,以供与大家交流学习。 关键词:厂房;钢结构;焊接技术 1、工程概述 某装焊厂房位于某工程有限公司内,建筑面积为22000平方米,为单层工业厂房,主体钢结构为门式钢架结构,轴线位置编号见图纸,为三跨结构,单跨跨度为32米,柱距为8米,共有116根主钢柱,203根主钢梁,336根吊车梁。门式钢架梁、柱及吊车梁钢材均采用Q345B,钢梁钢柱连接用高强螺栓均采用大六角级,摩擦面做喷砂处理。钢结构主构件采用抛丸除锈。该工程设计使用年限50年,结构安全等级为二级,抗震设防烈度为7度。焊接部位包括有:(1)上节柱与下节柱的对接接头;(2)钢梁与钢柱的对接接头。(3)钢梁上的栓钉焊接。 2、钢结构安装焊接前的准备 本工程使用的钢板在国内应用并不多,针对其中数量较多且具有代表性的接头形式进行了相应焊接方法的工艺评定试验。试验钢材包括Q345GJC-Z15(壁厚70mm)、Q345GJC-Z15(壁厚40mm)、Q345C(翼缘厚28mm),焊接位置为柱—柱横焊、柱—梁平焊(包括桁架梁上下翼缘平焊)、T型角立焊。坡口形式及尺寸按设计要求。焊后外观及超声波检查合格后取样进行了力学和物理试验。试验结果接头的抗拉强度达到母材抗拉强度标准值,接头弯曲180°无裂纹。采用的焊接材料和焊接设备技术条件应符合国家标准,性能优良。清渣、气刨、焊条烘干保温等装置应齐全有效。 手工电弧焊及CO2气保焊焊材和设备:(1)焊条应在高温烘干箱中烘干,焊条烘干次数不得超过两次。 (2)焊丝包装应完好,如有破损而导致焊丝污染或弯折、紊乱时应部分弃之。(3)CO2气体纯度应不低于(体积比),含水量应低于(重量比),瓶内高压低于1MPa时应停止使用。(4)焊机电压应正常,地线压紧牢固,接触可靠,电缆及焊钳无破损,送丝机应能均匀送丝,气管应无漏气或堵塞。 3、安装焊接程序及注意的规定要点 焊接的一般顺序为:焊前检查 →预热除锈 → 装焊垫板和引弧板→ 焊接 → 检验 具体来说:(1)同一节柱上的梁,先焊上层梁,后焊下层梁。(2)柱两侧对称的梁应同时焊接,同一根梁的两端不能同时焊接。(3)同一根梁的上下翼板应先焊下翼板,后焊上翼板。(4)从中部柱开始焊接,对称向外围焊接。(5)上下节柱的对接接头采用对称焊接,施焊时,应两人同时对称焊接一个接头,防止焊接变形引起柱弯曲。对称的两面先焊至1—3层,然后将另外对称的两个面焊满,再将未焊满的焊缝焊满。 规定与注意:(1)焊前检查坡口角度、钝边、间隙及错口量,坡口内和两侧的锈斑、油污、氧化铁皮等应清除干净。(2)预热。焊前用气焊或特制烤枪对坡口及其两侧各100mm范围内的母材均匀加热,并用表面测温计测量温度,防止温度不符合要求或表面局部氧化,预热温度。(3)重新检查预热温度,如温度不够应重新加热,使之符合要求。(4)装焊垫板及引弧板,其表面清洁程度要求与坡口表面相同,垫板与母材应贴紧,引弧板与母材焊接应牢固。(5)焊接:第一层的焊道应封住坡口内母材与垫板的连接处,然后逐道逐层累焊至填满坡口,每道焊缝焊完后,都必须清除焊渣及飞溅物,出现焊接缺陷应及时磨去并修补。(6)一个接口必须连续焊完,如不得已而中途停焊时,应进行保温缓冷处理,再焊前,应重新按规定加热。(7)遇雨、雪天时应停焊,构件焊口周围及上方应有挡风、雨棚,风速大于5m/s时应停焊。环境温度低于零度时,应按规定采取预热和后热 措施 施工。(8)碳素结构钢应在焊缝冷却到环境温度、低合金结构钢应在完成24h以后,进行焊缝探伤检验。(9)焊工和检验人员要认真填写作业记录表。 4、焊接施工中的重要工艺参数 4、1典形节点的焊接顺序和工艺参数 主要是:(1)上下柱无耳板侧由两名焊工在两侧对称焊至板厚的1/3处时,切去耳板。(2)然后在切去耳板侧由两名焊工在两侧对称焊至板厚的1/3处。(3)再由两名焊工分别承担相邻两面的焊接。(4)每两层之间焊道的接头应相互错开,两名焊工焊接的焊道接头也要注意每层错开,焊接过程中要注意检测层间温度。(5)焊接工艺参数,如下: 1)CO2气保焊:焊丝直径Φ,电流280~320A,焊速350~450mm/min 2)焊丝伸出长度:约20mm,气体流量25~80L/min, 3)电压:29~34V,层间温度120~150℃ 4、2柱—梁、梁—梁节点的处理 主要是:(1)先焊梁的下翼缘,梁腹板两侧的翼缘焊道要保持对称焊接。(2)待下翼缘焊完,然后焊接上翼缘。(3)如翼缘板厚大于30mm时,宜上下翼缘轮换施焊。(4)焊接工艺参数,如下: 1)CO2气保焊:焊丝直径φ,电流280~360A,焊速300~500mm/min 2)焊丝伸出长度:约20 mm,气体流量20~80L/mm 3)电压:30~38V,层间温度120~150℃ 5、结束语 钢结构安装焊接质量控制是一项综合技术,焊接质量受材料性能、工艺方法、设备、工艺参数、气候和焊工技术及情绪的影响。施工前根据工艺评定编制操作指导书,便于每个焊接人员明确操作要领、材料的使用和质量要求。施工过程中焊工做好焊前和焊接的记录,焊接工程师检查时逐条焊缝检查验收、做好记录,确保实体工程的安全使用。在该厂房主体工程竣工后,根据国家、行业相关要求对该工程进行了钢结构主体工程的鉴定,鉴定依据:(1)《钢结构工程施工质量验收规范》GB50205-2001;(2)《建筑结构检测技术标准》GB/T50344-200;(3)《建筑工程施工质量验收统一标准》GB50300-2001;(4)《建筑钢结构焊接规程》JGJ81-2002;(5)《钢焊缝手工超声波探伤方法和探伤结果分级》GB11345-1989;(6)某装焊车间厂房设计图纸。实际证明,该钢结构主体工程的施工安装质量符合GB50205-2001技术标准及设计要求,可以交付使用。 参考文献 1、陈海波。某装焊厂房钢结构工程鉴定[J],建筑科技与管理,2009年第11期 2、杨凌川,杨文柱。高层建筑钢结构安装焊接施工质量控制,重庆建筑大学学报[J],增刊2000,22:208-211 钢结构焊接技术论文篇三:《试谈建筑钢结构低温焊接施工技术》 摘 要:通过对低温环境条件下管道焊接施工措施的研究,并经工程实验,得出在低温环境条件下,影响焊接质量的因素更多的在于施工机具、焊接设备的适应性、焊工劳动防护措施的保暖性和轻便性等因素。 关键词:低温焊接;预热温度;焊后保温 随着焊接环境温度的降低,焊缝金属的硬度值增大。采取有效的预热、层间温度和焊后缓冷措施以降低焊缝金属的冷却速度,从而改善焊缝金属的硬度值。热温度不足的情况下,根焊缝产生裂纹的倾向性增加,但增加预热温度和改进预热方式,可明显提高焊缝质量。创造适合的施工环境和焊接条件,保证焊工劳动防护措施的保暖性和轻便性,焊接过程中使用自制的可移动式保温防风棚和管端封堵器等。 1.低温焊接时的施工工艺 由于是在低温环境中进行焊接作业,所以为了更好的完成焊接任务,应该尽量选取氢含量较低的焊接材料,并且对焊接材料进行必要的 烘焙 以及保温措施。为了达到尽量减少热量的损失,可以在进行焊接作业的地方构建相应的保护房,从而形成相对密闭的空间。如果条件不允许构建防护房,也可以采取其他一些措施来起到防护热量损失的作用。在进行一些气体保护焊接操作时,气瓶也要进行必要的保温措施。预热和层间温度。相比较于常温条件下的焊接预热,低温焊接时的预热温度要稍高,并且需要预热的区域范围较大,通常情况下是焊接点周围大于等于两倍钢厚度的范围,并且这一范围不小于100mm。焊接层的温度通常要高于预热温度,或者是不低于相应规定中的最低温度20℃,二者之间取较高温度者;采用合理的焊接方法。尽量使用窄摆幅,多层多道焊,严格控制层间温度;焊接后热及保温。焊接后及时对焊接接头进行后热保温处理。利于扩散氢气的逸出,防止因冷速过快而引起的冷裂纹,同时适当的后热温度还可以适当降低预热温度。 2.钢结构的焊接施工技术 焊接施工流程 施焊人员必须要熟悉图纸,做好焊接工艺技术交底,确保施焊人员执证上岗,明确焊工的焊接任务,然后进行现场验电,预热,后热温度试验确定等作业准备。然后选择合适的焊接工艺以及合适的焊接参数,并通过焊接实验验证。焊接工作开始,对焊口进行清理,检查坡口等是否符合要求,检查定位焊是否牢固,焊缝周围是否有油污和锈污。对焊材进行预热和保温,然后按照既定的焊接参数进行焊接,焊接完成后,对焊缝周围进行清渣处理,做好焊后保温工作,焊接完成。 焊材的选择和与钢材的匹配 与钢材的规定最低标准相比,焊材的金属强度,坚韧性,可塑性都要明显高于钢材本身,而且,在焊接接头的地方,各种基本性能指标都要与钢材规定的最低标准等同或比之更高;要保证焊缝的可塑性,钢材较厚时,要根据厚度选择合的焊材;选择合适韧性的焊材,韧性好的焊材可以提高焊缝和热影响区的韧性,使之能够满足钢结构的受力要求。 焊接质量控制 对输入的热和焊接冷却速度进行控制:通过控制焊接电压,焊接电流,接速度以及熔融金属的冷却速度等来对焊接质量进行控制。控制焊缝内元素组成进行控制:选择高质量的焊材,操作人员高超的操作手法和技巧,保证焊缝外观质量。选择能量密度高的,输入热量低的焊接方法,对焊接应力与变形进行控制。从钢材料的出发,考量各项技能的标准要求,选择合适的焊材以及评估焊接质量的试验方法,得出适合生产的焊接工艺,在焊接时,注意层间温度的控制,防止出现焊接接头弱化的现象。总之,尽量在最低成本的原则下,完成高质量的焊接任务。焊工须持双证上岗,即安全上岗证、焊工合格证。且具有相应的施焊资历。 3.高强钢焊接的施工工艺 焊接材料的选择及匹配 强节点弱杆件,即与母材规定的最低标准相比,焊接材料熔敷金属在强度、韧性、塑性等方面要明显高于标准;并且焊接接头位置的各种基本的性能指标至少要与母材料规定的最低标准相匹配;在进行厚板焊接时,应该根据厚度效应后的强度来选择适当的焊材,通常当节点的拘束度比较大的时候,可以在1/4 板厚以后选择强度稍低的焊材;对焊材韧性的选择是一项非常重要的工作,好韧性的焊材能够使焊缝以及热影响区的韧性满足钢结构的规定标准。比如在焊接无裂纹钢种的时候,可以选取低H 或者超低H 的焊接材料,同时,在钢板厚度低于50mm 或者温度在0℃以上的时候,可以不对钢结构进行预热。这一方法的明显优势就是它的力学指标突出,尤其是在区强比的冲击性能方面更显优越。 确定最低预热温度的常用方法 通过裂纹实验来进行控制,即通过进行斜Y 坡口试样抗裂方面的试验对最低的预热温度进行确认;通过硬度控制预热温度,通常采用的方法是根据一定碳含量的钢材,其不同板厚T 形接头角焊缝热影响区硬度达到350HV 对应的冷却速度(540℃时),查表确定焊接线能量;根据裂纹敏感指数、板厚范围、拘束度等级、熔敷金属扩散氢含量确定最低预热温度;根据接头热输入、冷却时间和钢材的特定曲线□确定最低预热温度。 对焊接质量的控制方法 对热输入以及冷却速度进行控制。此方法主要是通过对焊接时的电压、电流以及焊接时的焊接速度和熔敷金属在800℃~500℃区间内的冷却时间的控制,进而完成焊接质量的控制;对焊缝中各种元素的质量百分比进行必要的控制,主要是指碳、硫、磷、氢、氧等。为了达到这一目的,除了要选择质量优越的低氢焊接材料外,还要求操作人员拥有较好的操作手法,从而对熔池金属进行很好的保护;应力与变形控制。选用高能量密度、低热输入的焊接方法。 4.结束语 最后得到适合于生产的焊接工艺,起到相应的指导生产的要求。在进行这一钢材的焊接时,为了避免其产生冷裂现象,应该注意采取相应的措施。同时为了出现接头弱化的现象,焊接时应该对层间温度以及焊接线能量进行较为严格的筛选和控制。总的原则还是应该在较低的成本下,尽可能完成高质量的焊接任务。 参考文献: [1]姚晋勇.论钢结构焊接现场施工工艺[J].科技情报,2012 [2]徐鹏毅.钢结构焊接现场施工工艺探讨[J].中国地产,2013 猜你喜欢: 1. 电焊工个人简历模板 2. 钢结构安全管理论文 3. 钢结构施工管理论文范文 4. 钢结构职称论文 5. 锅炉焊接技术论文
土木工程专业的英文论文格式
导语:土木工程专业的英文的论文格式包括哪些内容呢?土木工程是建造各类工程设施的科学技术的统称。下面是我分享的土木工程专业的英文的论文格式,欢迎阅读!
土木工程专业的英文论文格式均以美国土木工程师协会出版社发布的标准格式为准。
英语论文用激光打印机打印,打印稿为黑白稿,彩色打印件会影响出版效果。
版心:a4纸,上、下页边距 cm,左、右页边距均为 mm。论文内容宽不得超过, 长不得超过。
字体和字号:正文,标题,作者联络信息和图表中的文字均为times new roman 12号字。可以跟据需要使用同类字体中的粗体,斜体。
行距:单倍行距。
页码: 论文正文和文后所附图例都需添加页码。页码为阿拉伯数字,位于页面下方居中。
文体: 文章应语法正确,技术用词准确。标题应该以最简洁的语言概括文章内容。如果标题较长,请采用title: subtitle的形式。
数学公式:文中的数学公式不得手写,必须打印。公式如果在文中多次被引用,应该编号。公式之间,公式和正文之间都应该空一行。 单位: 文中所用的度量衡单位应为国际单位。可在括号内,单位对应表中列出其他单位。有关国际单位的使用(standard practice for use of the international system of units)可以通过电话1-向asce索取。其他相关使用参考文献,如anmc metric editorial guide, 5th ed,1992 可向美国国家公制协会 索取(american national metric council, 1735n. lynn street, suite 950, arlington, va 22209-2022)
图表:
标题说明和图例:插入的图表应该以出现顺序编号(figure 1,figure 2,table 1,table 2)。图的说明和标题,包括图的序号应该位于图的下方。表的说明和标题,包括表的序号应该位于表格上方。
位置: 图可以插入到正文中,或者集中放在文章最后。如果在正文中插入图,尽量放在页面的.顶部或尾部。不要选择文字环绕图形的对齐方式,可选择上下环绕方式。
底纹: 插图中不要选择带阴影或底纹,否则会影响印刷效果。
照片:如果文中需要附上照片,在文中出现照片的地方贴上其黑白光面冲洗照片,标题说明位于照片下方。照片将和正文一起缩印,请不要提供彩色照片,以免影响印刷效果。
扫描图: 印刷后的扫描图不如原件清晰。如果文中有扫描图,请提供灰色色标扫描图。
作者联络信息:请用横线和正文隔开。联络信息可以为一位作者或所有作者的,包括以下内容:作者全名;所属学会;学历或授予的荣誉;所在单位;通讯地址和电子邮箱;电话和传真。
参考文献: 所有参考文献为单倍行距,放在文章最后,按照第一作者姓氏的字母顺序排列。如有同一作者的两篇以上文献,按出版年代先后排列。正文中引用参考文献时,作者和出版年代应该放入括号内。由于上标缩印后会变小,难于辨认,正文中不使用上标标注参考文献。所列出的参考文献应当在正文中都有所引用,如果正文中没有引用,请将文献列入文章最后的附加信息(additional information)部分,或者相关材料(related materials)部分。
1.《建筑结构制图标准》GB/T50105-2001
2.《建筑结构荷载规范》GB5009-2001(2006版)
3.《混凝土结构设计规范》GB50010-2002
4.《建筑地基基础设计规范》GB5007-2002
5.《砌体结构设计规范》GB5003-2001
6.《建筑抗震设计规范》GB5011-2001
7.《钢结构设计规范》GB50017-2003
8.《建筑结构构造资料》(合订本),中国建筑工业出版社,1998年。
9.《混凝土结构构造手册》,中国建筑工业出版社,2002年。
10.《地基基础设计手册》,上海科技出版社,1998年。
11.《混凝土结构设计手册》,中国建筑工业出版社,2002年。
12.《建筑结构静力计算手册》,中国建筑工业出版社,1999年
13.《建筑结构强制性国家标准》(简装本),中国建筑工业出版社,2001年9月
14. 任全宏、常建军.钢筋混凝土多层框架结构房屋结构设计中应注意的几个问题。陕西建筑2007,145(7).
15. 范俊梅. 钢筋混凝土多层框架结构设计问题分析. 科技资讯2008,3.
16. Basic Principles for Reinforced Concrete Structure Design
17.建筑、结构设计有关图集资料以及专业课程教材等。
Traditional Construction ProceduresAs mentioned before, construction under the traditional construction procedure is performed by contractors. While they would like to satisfy the owner and the building designers, contractors have the main objective of making a profit. Hence, their initial task is to prepare a bid price based on an accurate estimate of construction costs. This requires development of a concept for performance of the work and a construction time schedule. After a contract has been awarded, contractors must furnish and pay for all materials, equipment, power, labor, and supervision required for construction. The owner compensates the contractors for construction costs and general contractor assumes overall responsibility for construction of a building. The contractor engages subcontractors who take responsibility for the work of the various trades required for construction. For example, a plumbing contractor installs the plumbing, an electrical contractor installs the electrical system, and an elevator contractor installs elevators. Their contracts are with the general contractor, and they are paid by the general , in addition to a general contractor, the owner contracts separately with specialty contractors, such as electrical and mechanical contractors, who perform a substantial amount of the work require for a building. Such contractors are called prime contractors. Their work is scheduled and coordinated by the general contractor, but they are paid directly by the also, the owner may use the design-build method and award a contract to an organization for both the design and construction of a building. Such organizations are called design-build contractors. One variation of this type of contract is employed by developers of groups of one-family homes or low-rise apartment buildings. The homebuilder designs and constructs the dwellings, but the design is substantially completed before owners purchase the of the construction procedure often is difficult. Consequently, some owners seek assistance from an expert, called a professional construction manager, with extensive construction experience, who receives a fee. The construction manager negotiates with general contractors and helps select one to construct the building. Managers usually also supervise selection of subcontractors. During construction, they help control costs, expedite equipment and material deliveries, and keep the work on schedule. In some cases, instead, the owner may prefer o engage a construction program manager, to assist in administrating both design and contractors employ labor that may or may not be unionized. Unionized craftspeople are members of unions that are organized by construction trades, such as carpenter, plumber, and electrician unions, Union members will perform only the work assigned to their construction, all work should be inspected. For this purpose, the owner, often through the architect and consultants, engages inspectors. The field inspectors may be placed under the control of an owner’s representative, who may be titled clerk of the works, architect’s superintendent, engineer’s superintendent, or resident engineer. The inspectors have the responsibility of ensuring that construction meets the requirements of the contract documents and is performed under safe conditions. Such inspections may be made at frequent addition, inspections also are made by representatives of one or more governmental agencies. They have the responsibility of ensuring that construction meets legal requirements and have little or no concern with detailed conformance with the contract documents. Such legal inspections are made periodically or at the end of certain stages of construction. One agency that will make frequent inspections is the local or state building department, whichever has jurisdiction. The purpose of these inspections is to ensure conformance with the local or state building is a description of the basic traditional construction procedure for a multistory the award of a construction contract to a general contractor, the owner may ask the contractor to start a portion of the work before signing of the contract by giving the contractor a letter of intent or after signing of the contract by issuing a written notice to proceed. The contractor then obtains construction permits, as required, form governmental agencies, such as the local building, water, sewer, and highway general contractor plans and schedules construction operations in detail and mobilizes equipment and personnel for the project. Subcontractors are notified of the contract award and issued letters of intent or awarded subcontracts, then are given, at appropriate times, notices to construction starts, the general contractor orders a survey to be made of adjacent structures and terrain, both for the record and to become knowledgeable of local conditions. A survey is then made to lay out offices for the contractor are erected on or near the site. If desirable for safety reasons to protect passersby, the required to be removed from the site are demolished and the debris is carted , the site is prepared to receive the building. This work may involve grading the top surface to bring it to the proper elevations, excavating to required depths for basement and foundations, and shifting of utility piping. For deep excavations, earth sides are braced and the bottom is construction starts with the placement of foundations, on which the building rests. This is followed by the erection of load-bearing walls and structural framing. Depending on the height of the building, ladders, stairs, or elevators may be installed to enable construction personnel to travel from floor to floor eventually to the roof. Also, hoists may be installed to lift materials to upper levels. If needed, temporary flooring may be placed for use of the building rises, pipes, ducts, and electric conduit and wiring are installed. Then, permanent floors, exterior walls, and windows are constructed. At the appropriate time, permanent elevators are installed. If required, fireproofing is placed for steel framing. Next, fixed partitions are built and the roof and its covering are put is place,Finishing operations follow. There include installation of the following: ceilings; tile; wallboard; wall paneling; plumbing fixtures; heating furnaces; air-conditioning equipment; heating and cooling devices for rooms; escalators; floor coverings; window glass; movable partitions; doors; finishing hardware; electrical equipment and apparatus, including lighting fixtures, switches, transformers, and controls; and other items called for in the drawings and specifications. Field offices, fences, bridges, and other temporary construction must be removed from the site. Utilities, such as gas, electricity, and water, are hooked up to the building. The sit is landscaped and paved. Finally, the building interior is painted and owner’s representatives then give the building a final inspection. If they find that the structure conforms with the contract documents, the owner accepts the project and gives the general contractor final payment on issuance by the building department of a certificate of occupancy, which indicates that the completed building meets building-code requirements.传统的施工程序众所周知,在传统的施工程序中进行施工的承包商。尽管他们想满足业主和建筑设计师的要求,但是最终还是以赚取利润为主要目标的。因此,他们最初的任务是对编写投标价格的建筑成本进行准确的估计。这就需要进行前期调查的工作并且做出施工时间表。等合约批出后,施工方必须提供所有材料并支付其费用,设备,电力,劳动力。业主此时需要进行必要的监督。一个总承包商承担一个建筑整体的责任。从事分包的承建商则需承担建造工程所需的各个工作。例如,管道承包商安装水管,电业承办商安装电气系统,电梯则由电梯承包商安装。他们与总承包商签订合同,费用由总承包商支付。有时候,除了一个总承包商,还有各种专业承包商,如电气和机械承包商,执行工作时需要与业主签订合同。这种承包商被称为间接承包商。他们的工作,由总承包商协调,但它们都是由业主直接联系。还有些时候,业主可以使用设计建造方法同时兼有设计和建筑施工单位的职能。这些单位被称为设计建造承包商。这方面的一个类型的合同聘用的变化是由一户住宅或低层住宅建筑群的开发。在房屋建筑设计和建造的住房,但设计之前需要由购买房屋的业主完成。施工过程管理往往是困难的。因此,一些业主会去寻求专家的协助,这些专家被称为专业施工经理,他们具有丰富的施工经验。施工经理与总承包商进行谈判,并选择其中一个项目。施工经理通常还监督分包商。在施工期间,它们有助于控制成本,加快运送设备和材料,并保持工作的进度。在依法行政,协助设计和建设的情况下,业主可以选择从事建筑项目经理。建筑承包商雇用的劳动力,一般有大工和小工。大工再建筑工程中从事技术活,如木工,管道工,工会成员和电工工会,小工则执行了分配给他们的工作。在施工期间,一切工作都要验收。因此,业主通过建筑师和监理经常进行督查。可能是名为工程员,建筑师或驻地工程师。作为业主的代表实地视察。核查人员必须确保工程符合合同文件的要求,并在安全的条件下进行的责任。这种检查可作出重复。此外,验收还是需要一个或多个政府机构的代表。他们必须确保工程符合法律要求,并负责检查与合同文件是否一致。这种视察一般定期或在某些阶段施工结束以后进行。地方或国家建设部门具有管辖权。这些检查的目的是确保符合当地或国家的建筑规范。以下是传统多层建筑施工的基本程序。建造开始后合同授予开发商,业主可要求开发商开始施工之前签约给或之后签约发出书面通知的同时另一部分工作继续进行。紧接着施工方根据需要获取建筑许可证,例如当地的建设,供水,污水处理,政府机构和公路部门。总承包商的计划和进度详细施工作业以及动员项目设备和人员。分包商得到通知后,做出签订合同的意向或授予分包合同书,然后给出在适当的时候进行通知。在施工前启动,总承包商要进行的一项调查就是邻近结构和地形,这些都要记录在案,并要熟悉当地情况。这项调查结束以后,随即进行布局建设。承建商的现场办事处都建在施工现场或附近。为了安全起见,必须从脚手架上移除的东西,产生的碎片都要运走。下一步,该网架是为建设工程准备的。这项工作为地下室开挖和基础开挖的深度,以及公用事业管道转移找到正确的标高。深挖掘,土方支撑,底部排出。建筑开始于基础上,然后是承重墙和结构框架的施工。梯子,楼梯,或电梯的安装,可让施工人员往返于各个楼层。此外,可安装卷扬机来运送材料。由于建筑高度的上升,管道,电力管道和线路安装以及永久地板,外墙,窗户和构造的影响。在适当的时候,永久的电梯安装。再需要的情况下可以安装防火卷帘。其次,屋顶等地方也需要安装。精加工工序安装有包括以下内容:天花板,瓷砖,墙板,墙壁镶板,水管装置,加热炉,空气调节设备,加热和冷却室装置;自动扶梯;地板,窗户玻璃;活动板,门;电气设备和仪器,包括照明灯具,开关,变压器,控制器,遵照项目的图纸和规格。外地办事处,围栏,桥梁和其他临时建筑,公共设备,如天然气,电力管道,水管,都连接到建筑上。最后,是建筑物内部的打扫和清洗。业主的代表,会给建设工程作最后检查。如果他们满意并认为符合合同文件,那么业主接受该项目,并交给总承包商的一个占用证书,这表明,总承包商已完成建设,建设部门再根据建筑规范的要求发放最后付款。
钢结构课程设计论文
在平时的学习、工作中,大家都跟论文打过交道吧,论文是指进行各个学术领域的研究和描述学术研究成果的文章。相信许多人会觉得论文很难写吧,下面是我为大家收集的钢结构课程设计论文,仅供参考,欢迎大家阅读。
一、钢结构课程设计中存在的问题
(一)钢结构课程设计选题单一
高校钢结构课程设计选题较为单一,一般为钢屋架设计或钢梁设计。钢结构课程设计在钢结构课程教学完成几周后才进行,有的甚至到学期末,内容讲授与设计实践严重脱节。学生在一周或两周课程设计中,往往只能完成一种普通钢屋架的设计,内容较为单一,还会出现较多弊端。如钢屋架设计,因为钢屋架可以看成厂房设计当中的一个构件,学生在设计过程中缺少整体结构设计的概念,钢屋架的设计的实际应用范围有限。钢屋架的连接计算程式化的东西过多,连接计算过于单调、重复量过大。
(二)学生识图和制图能力较差
在近些年的钢结构课程设计教学和指导中,笔者发现由于部分学生的空间想象能力较差,往往对屋盖支撑系统的布置及关系不清楚,有些学生在进行屋盖结构布置图中常常出错。对于一榀钢屋架详图的绘制,由于图面表达内容较多,涉及的构造做法较多,学生在连接节点处内容表述不够完整,屋架的剖视图不相对应。学生在绘制钢屋架的施工图时常常不能正确地表达设计意图。在平时的学习过程中学生接触的混凝土结构设计施工图较多,而对钢结构设计的施工图较少。在有限的课堂时间内,学生要真正看懂钢结构施工图,正确表达自己的设计意图并非易事,所以学生在做钢结构课程设计时,常常照搬照抄课本或课程设计指导书中钢屋架的施工图纸,甚至出现设计图纸上的尺寸结果和设计计算书中的计算结果不一致的情况。
(三)学生的创新意识不够
钢结构课程设计中的屋架设计由于教师已给定了屋架的跨度及桁架的`尺寸,所以学生在做设计时不去查阅相关设计规范和设计资料,更不会考虑比选设计方案,学生的主观能动性受到了限制。因此,教师在布置课程设计任务时,要精心选题,给学生充足的空间,鼓励学生自己查阅资料,确定设计方案和尺寸,以确保学生主观能动性的发挥。此外,教师要给学生提供一个交流学习的平台,组织学生开展讨论、交流,让学生在此过程中发现问题、分析问题,从而不断培养创新思维和创新意识。针对上述钢结构课程设计存在的问题,笔者对目前钢结构课程设计的命题、教学和考核方法进行改进,提出了切实可行的建议和措施。
二、钢结构课程设计教学改革的构想与实践
(一)精选设计题目,分组设计,一人一题
教师在选择课程设计题目时,应该根据学生学习能力的差异,精心选择并布置多种形式的课程设计题目。除了钢屋架设计外,还可以选轻型门式刚架、平台结构设计、钢框架设计等题目。为了培养学生的独立思考能力,避免学生在设计过程中出现抄袭现象,在课程设计中可采用分组设计和一人一题的方法。4~5人一组,设计同一种结构型式的题目。如设计钢屋架的小组,可通过改变设计条件及参数等方式,实现一人一题。又如屋架的选择形式多样,学生可选择梯形屋架、三角形屋架或人字形屋架进行设计。荷载的取值可提供多种组合。通过这种分组设计的方式,巩固学生的理论知识,锻炼学生的设计能力,加强和培养学生的沟通协作能力和团队协助精神。
(二)改革钢结构课程设计的教学方法
以课堂教学为平台,将课程设计融入到课堂教学中,再将课程设计中涉及到的主要内容分解成若干专题做重点介绍,并要求学生根据分组布置的安排在每个专题讲完后开展讨论,将遇到的问题及时反馈,教师在后续阶段集中重点解答。通过这种方式,教师就能及时解决学生遇到的问题,有的放矢,在课堂教学中根据不同的内容选择不同的教学方法。如:对构件的力学分析时采用板书讲解,可以让学生逐步了解和掌握构件从外力到内力再到结构稳定的整个过程。除采用传统的教学方法外,还应采用多媒体辅助教学。对于桁架的设计,此部分教学内容比较抽象,应利用多媒体进行授课。对节点部分的构造做法和施工焊接流程可采用大量的工程图片、动画演示以及录像资料作演示,让学生身临其境。现代教学手段所提供的感性材料使教学活动更加生动有趣。视觉和听觉的刺激可以加深感知度,提高教学效率和学习质量。
(三)建立钢结构课程设计的网络教学平台
为便于学生课后学习,教师可利用学校提供的网络教学平台建立钢结构课程设计课程网站,内容可包括课程负责人介绍、教学队伍、教学计划及大纲、课件、工程图片、教学动画演示、教学录像、学习参考资料目录、作业习题、友情链接等,还可提供钢结构设计的规范和图集等设计资料。学生可以随时访问此网站,获取所需相关知识,实现教师与学生之间的互动,开阔学生视野,扩宽知识面,网站还专门设置了重要学术杂志如《土木工程学报》、《建筑结构学报》、《建筑结构》、《工业建筑》、《钢结构》及《现代钢结构进展》等链接,以方便学生与钢结构专家直接交流。
(四)增设教学实习环节,提高教学效果
为提高钢结构课程设计的教学效果,增加学生对钢结构设计的感性认识,教师要积极联系适合现场教学的钢结构工地,带学生实地观察钢结构的空间构造与一些局部的连接构造。学生在教师或工程师的带领下按照结构布置、构件做法及节点连接方式的顺序依次参观。这种教学实习,便于学生学习钢结构施工图,逐步建立所设计结构的整体空间概念。
(五)改革课程设计的考核方式
教师在评阅课程设计时主要依据学生完成的设计说明书、设计图纸进行,然后由指导教师定性给出考核等级。这样的考核方式存在考核不客观、考核成绩不能有效反映学生的真实学习水平,没有给学生一个更为公平、公正、合理的评价。所以要真实客观地反映学生的学习成果,就要综合考虑各个影响课程设计效果的环节,比如可以借鉴毕业设计考核方式,增设学生的课堂答辩。课堂答辩一方面可以充分调动学生的学习积极性;另一方面通过答辩环节,教师可以比较全面地了解学生设计的真实水平,从而客观地给出考核成绩。同时,课堂答辩过程也是学生设计过程中的经验和心得交流的一次机会,通过这个平台,学生可以进一步学习其他同学设计中的一些长处,发现自己设计的不足并加以改进。要建立完善的课程设计考核体系,将体现设计成绩的各个过程细化。比如综合多方面因素给出考核成绩:考核总成绩=平时考勤×0.1+设计说明书成绩×0.2+设计图成绩×0.3+答辩成绩0.3+创新成绩×0.1。针对以往课程设计中存在的学生创新意识不够的问题,教师要鼓励并肯定学生设计中创新性行为。课程设计不仅是一个熟悉设计方法的过程,更应该成为培养学生创新能力的机会,所以要鼓励学生大胆创新,在成绩评定方面也要有所体现。
三、结语
钢结构课程设计是一门实践性很强的专业课程,对培养学生分析和解决工程设计问题的能力起到十分重要的作用。重视钢结构课程设计,使在校学生在钢结构设计方面得到锻炼,为毕业从事钢结构方面的工作打基础,已成为钢结构教学改革的当务之急。针对目前钢结构课程设计教学中存在的问题,提出钢结构课程设计需要改进的措施,以期对钢结构课程设计改革有所裨益。
In the past decade, the concept of a second-order or an advanced analysis has been described in various national design codes of practice such as the Load and Resistance Factor Design Specifi- cation for Structural Steel Buildings ( 1986 ) and the Australia standards ( AS4100 1990 ) . Unlike the 1inear analysis where checking of member strength against instability and second-order effect is carried out by the element design formulas in the codes, the second-order analysis automatically includes the effects of these nonlinear terms. As aresult of this, stress, allowing for the second- order P-δand P-△ effects,can be automatically computed and compared with the factored yield stress, or the design strength, in the analysis so that the empirical approach to amplify the moment due to a large change of geometry becomes unnecessary, resulting in much convenience and accuracy. In addition, the second-order and advanced analysis--including various linear and nonlinear terms for a more accurate computation of member forces and moments-provides a much more effective and accurate means of assessing the strength, stability, and serviceability of a structure and is expected to be widely accepted by the engineer, provided that an effective and robust analysis method is available This "integrated design and analysis approach "is aimed at using a sophisticated second-order analysis to design practical steel frames fulfilling the design code requirements. A literature survey shows that typical second-order analysis methods ignore many important characteristics and requirements for practical design, including the member initial imperfection and its direction, consistency between the linear and the nonlinear models due to the need to use several elements per member for a second-order analysis, and loads along members. The proposed method includes these terms so that it can be used to directly design real and practical steel frames fulfilling the advanced analysis requirement.中文翻译过去十年中,二阶或高等分析的概念在各种国内设计规范中被描述,例如结构钢建筑负载和抗性因子设计规格( 1986 ) 和澳大利亚标准 ( AS4100 1990 ) 。不同于线性分析用规范中的元设计方程来执行构件强度反不稳定性和二阶效应的检查,二阶分析自动地包括这些非线性条件的效果。结果是应力允许二阶P-δ和P-△效应,可被自动地计算并与屈服应力或设计强度相比较,以便在分析中不再需要因几何形状的巨变而扩大力矩的经验方法,结果更方便、精确。此外,二阶与高等分析--包括更精确的构件力-力矩计算的各种线性和非线性条件,并提供更有效和更精确的结构强度、稳定性和适用性估计方法,可望被工程师广泛接受,提供一个有效的分析法是可行的。"综合设计和分析进展"针对使用复杂的二阶分析去实施规范需要的应用钢框架设计。一篇文献调查认为典型的二阶分析法忽视了许多重要的特性和实践设计需要,包括构件初始不完整性和它的方向,线性和非线性模型之间的一致性因为需要对每构件几个元件作二阶分析,和沿构件的负载。建议的方法包括这些条款以便它能直接用于实现高等分析要求的设计和应用钢框架。
好多分哦...送我好吗?
毕业论文,泛指专科毕业论文、本科毕业论文(学士学位毕业论文)、硕士研究生毕业论文(硕士学位论文)、博士研究生毕业论文(博士学位论文)、博士后毕业论文等,即需要在学业完成前写作并提交的论文,是教学或科研活动的重要组成部分之一。毕业设计一般是理工科学生毕业答辩前的功课,要自已设计一套系统(各专业要求不一样),比如软件专业要设计一个程序或者是某个小型数据库之类的,再来证明其可行性,理论基础等。由此形成的对于这个设计的解释性文字就是毕业论文。 如果是文科专业的,就没有毕业设计,只有毕业论文了
1、毕业论文主要是以文字叙述为主,穿插着各种实例的东西,一般会让你附带什么什么的计算啊体会啊等等。而大学院校的毕业设计是一个设计过程,比如施组设计、钢结构设计,从预算开始,画施工图,算工程量,以及其中的各项计算(如脚手架稳定性、基坑开挖的相关计算、场地平整之类的),很麻烦。2、答辩老师一般都是你的毕业设计老师,他们基本都知道你设计的具体情况,毕竟你如果学习不是很好,我教你个办法就是多和老师处处关系,多问问老师问题,老师去设计教室的时候你一定都要在,出勤率高的话老师会对你印象好的,而且多问问老师问题老师也会帮助你呀,会在你答辩的时候问你提过的问题,这样你不是很好解决了嘛,我记得我那会也是学习不杂好,老师很关照我的,只要听老师话,完成老师布置的任务就好了。3、网上的东西只能做参考,除非里面的英语翻译啊之类的建筑专业不是很精通的可以在网上找找翻译,其他的最好自己和同班的同学一起参考着来做,其实还有个方法,就是同一课题的毕业设计在你上一届的同学他们就做过,你如果可以找到的话。。。。参考参考啊只能。。。抄袭老师是看的出来的!动动脑子!4、专科的毕业设计很好弄的,就看你肯不肯下功夫,我毕业设计是答辩前一个月左右才弄的,多参考下老师的意见,和老师说说就说自己水平不是很高希望老师能帮助帮助你,老师不讨厌诚恳的学生,讨厌的是耍滑的学生。哈哈,我就一直按老师给我布置的来做,结果老师就让我过了,答辩时也没为难我哦。祝你好运哦!!!不过真的希望你能从毕业设计上学到点东西,毕竟要工作了,出来你就知道了,一工作就知道自己肚子里什么都没了。我绝对是亲身体验,现在天天抱个书学习,你要养活自己就要靠这最后的毕业设计来充充电哦。。。希望你自己体会体会我的话,对你会有帮助的!
毕业设计与毕业论文有什么区别?为什么有的专业写毕业论文?毕业设计是毕业的一种设想和打算。而毕业论文世说自己的毕业成果。
钢结构课程设计论文
在平时的学习、工作中,大家都跟论文打过交道吧,论文是指进行各个学术领域的研究和描述学术研究成果的文章。相信许多人会觉得论文很难写吧,下面是我为大家收集的钢结构课程设计论文,仅供参考,欢迎大家阅读。
一、钢结构课程设计中存在的问题
(一)钢结构课程设计选题单一
高校钢结构课程设计选题较为单一,一般为钢屋架设计或钢梁设计。钢结构课程设计在钢结构课程教学完成几周后才进行,有的甚至到学期末,内容讲授与设计实践严重脱节。学生在一周或两周课程设计中,往往只能完成一种普通钢屋架的设计,内容较为单一,还会出现较多弊端。如钢屋架设计,因为钢屋架可以看成厂房设计当中的一个构件,学生在设计过程中缺少整体结构设计的概念,钢屋架的设计的实际应用范围有限。钢屋架的连接计算程式化的东西过多,连接计算过于单调、重复量过大。
(二)学生识图和制图能力较差
在近些年的钢结构课程设计教学和指导中,笔者发现由于部分学生的空间想象能力较差,往往对屋盖支撑系统的布置及关系不清楚,有些学生在进行屋盖结构布置图中常常出错。对于一榀钢屋架详图的绘制,由于图面表达内容较多,涉及的构造做法较多,学生在连接节点处内容表述不够完整,屋架的剖视图不相对应。学生在绘制钢屋架的施工图时常常不能正确地表达设计意图。在平时的学习过程中学生接触的混凝土结构设计施工图较多,而对钢结构设计的施工图较少。在有限的课堂时间内,学生要真正看懂钢结构施工图,正确表达自己的设计意图并非易事,所以学生在做钢结构课程设计时,常常照搬照抄课本或课程设计指导书中钢屋架的施工图纸,甚至出现设计图纸上的尺寸结果和设计计算书中的计算结果不一致的情况。
(三)学生的创新意识不够
钢结构课程设计中的屋架设计由于教师已给定了屋架的跨度及桁架的`尺寸,所以学生在做设计时不去查阅相关设计规范和设计资料,更不会考虑比选设计方案,学生的主观能动性受到了限制。因此,教师在布置课程设计任务时,要精心选题,给学生充足的空间,鼓励学生自己查阅资料,确定设计方案和尺寸,以确保学生主观能动性的发挥。此外,教师要给学生提供一个交流学习的平台,组织学生开展讨论、交流,让学生在此过程中发现问题、分析问题,从而不断培养创新思维和创新意识。针对上述钢结构课程设计存在的问题,笔者对目前钢结构课程设计的命题、教学和考核方法进行改进,提出了切实可行的建议和措施。
二、钢结构课程设计教学改革的构想与实践
(一)精选设计题目,分组设计,一人一题
教师在选择课程设计题目时,应该根据学生学习能力的差异,精心选择并布置多种形式的课程设计题目。除了钢屋架设计外,还可以选轻型门式刚架、平台结构设计、钢框架设计等题目。为了培养学生的独立思考能力,避免学生在设计过程中出现抄袭现象,在课程设计中可采用分组设计和一人一题的方法。4~5人一组,设计同一种结构型式的题目。如设计钢屋架的小组,可通过改变设计条件及参数等方式,实现一人一题。又如屋架的选择形式多样,学生可选择梯形屋架、三角形屋架或人字形屋架进行设计。荷载的取值可提供多种组合。通过这种分组设计的方式,巩固学生的理论知识,锻炼学生的设计能力,加强和培养学生的沟通协作能力和团队协助精神。
(二)改革钢结构课程设计的教学方法
以课堂教学为平台,将课程设计融入到课堂教学中,再将课程设计中涉及到的主要内容分解成若干专题做重点介绍,并要求学生根据分组布置的安排在每个专题讲完后开展讨论,将遇到的问题及时反馈,教师在后续阶段集中重点解答。通过这种方式,教师就能及时解决学生遇到的问题,有的放矢,在课堂教学中根据不同的内容选择不同的教学方法。如:对构件的力学分析时采用板书讲解,可以让学生逐步了解和掌握构件从外力到内力再到结构稳定的整个过程。除采用传统的教学方法外,还应采用多媒体辅助教学。对于桁架的设计,此部分教学内容比较抽象,应利用多媒体进行授课。对节点部分的构造做法和施工焊接流程可采用大量的工程图片、动画演示以及录像资料作演示,让学生身临其境。现代教学手段所提供的感性材料使教学活动更加生动有趣。视觉和听觉的刺激可以加深感知度,提高教学效率和学习质量。
(三)建立钢结构课程设计的网络教学平台
为便于学生课后学习,教师可利用学校提供的网络教学平台建立钢结构课程设计课程网站,内容可包括课程负责人介绍、教学队伍、教学计划及大纲、课件、工程图片、教学动画演示、教学录像、学习参考资料目录、作业习题、友情链接等,还可提供钢结构设计的规范和图集等设计资料。学生可以随时访问此网站,获取所需相关知识,实现教师与学生之间的互动,开阔学生视野,扩宽知识面,网站还专门设置了重要学术杂志如《土木工程学报》、《建筑结构学报》、《建筑结构》、《工业建筑》、《钢结构》及《现代钢结构进展》等链接,以方便学生与钢结构专家直接交流。
(四)增设教学实习环节,提高教学效果
为提高钢结构课程设计的教学效果,增加学生对钢结构设计的感性认识,教师要积极联系适合现场教学的钢结构工地,带学生实地观察钢结构的空间构造与一些局部的连接构造。学生在教师或工程师的带领下按照结构布置、构件做法及节点连接方式的顺序依次参观。这种教学实习,便于学生学习钢结构施工图,逐步建立所设计结构的整体空间概念。
(五)改革课程设计的考核方式
教师在评阅课程设计时主要依据学生完成的设计说明书、设计图纸进行,然后由指导教师定性给出考核等级。这样的考核方式存在考核不客观、考核成绩不能有效反映学生的真实学习水平,没有给学生一个更为公平、公正、合理的评价。所以要真实客观地反映学生的学习成果,就要综合考虑各个影响课程设计效果的环节,比如可以借鉴毕业设计考核方式,增设学生的课堂答辩。课堂答辩一方面可以充分调动学生的学习积极性;另一方面通过答辩环节,教师可以比较全面地了解学生设计的真实水平,从而客观地给出考核成绩。同时,课堂答辩过程也是学生设计过程中的经验和心得交流的一次机会,通过这个平台,学生可以进一步学习其他同学设计中的一些长处,发现自己设计的不足并加以改进。要建立完善的课程设计考核体系,将体现设计成绩的各个过程细化。比如综合多方面因素给出考核成绩:考核总成绩=平时考勤×0.1+设计说明书成绩×0.2+设计图成绩×0.3+答辩成绩0.3+创新成绩×0.1。针对以往课程设计中存在的学生创新意识不够的问题,教师要鼓励并肯定学生设计中创新性行为。课程设计不仅是一个熟悉设计方法的过程,更应该成为培养学生创新能力的机会,所以要鼓励学生大胆创新,在成绩评定方面也要有所体现。
三、结语
钢结构课程设计是一门实践性很强的专业课程,对培养学生分析和解决工程设计问题的能力起到十分重要的作用。重视钢结构课程设计,使在校学生在钢结构设计方面得到锻炼,为毕业从事钢结构方面的工作打基础,已成为钢结构教学改革的当务之急。针对目前钢结构课程设计教学中存在的问题,提出钢结构课程设计需要改进的措施,以期对钢结构课程设计改革有所裨益。
摘要:柱脚是钢结构中上部主体结构与基础连接的重要节点,文章对铜结构的埋入式和外包式柱脚的抗震设计进行分析。
关键词:钢结构柱脚;埋入式;外包式
1.通常钢结构的柱脚形式有外包式柱脚,埋入式柱脚及外露式柱脚3种
外包式柱脚指将钢柱脚外面用钢筋混凝土包住的柱脚,埋入式柱脚是把钢柱固定在混凝土的基础梁上柱脚,而外露式柱脚是在混凝土基础表面固定钢柱的柱脚,其也是最常用的钢结构柱脚。钢结构柱脚,反力特别大,因此设计规划时一般采用固定柱脚。在此类情况下,采用外露式柱脚不仅会导致底板既大又厚,消耗大量钢材,更重要的是难以确保柱脚被完全固定。外包式柱脚和埋入式柱脚钢结构固定式柱脚的很好的选择,通常抗震设计也用这两类柱脚。
2.埋入式柱脚抗震设计
埋入式柱脚的特点,是将钢柱以一定深度埋置在混凝土基础梁中,埋人部分的钢柱表面虽然焊有栓钉,但根据研究,在这种形式的柱脚中栓钉的作用不大,内力的`传递主要依靠混凝土对钢柱翼缘的承压力,柱的轴向压力可由柱脚底板传给混凝土,柱的轴向拉力可由柱脚底板伸出部分对混凝土的承压作用传给混凝土,或由锚栓传给基础。埋入式柱脚的支配因素是埋入深度。试验表明,对于轻型工字形柱,埋深与柱截面高度之比不得小于2,对于大截面的宽翼缘H形柱和箱形柱,埋深与截面高度之比不得小3,且同时应满足下式要求:
d>=(6M/bf*fc)
d-柱脚埋深;M-柱脚全截面屈服时的极限弯矩;bf-柱在受弯方向截面翼缘的宽度;fc-基础混凝土轴心受压强度设计值。
柱脚轴向压力由柱脚底板直接传给基础,按现行国家标准《混凝土结构设计规范》GB50010-2010验算柱脚底板下混凝土的局部承压,承压面积为底板面积。
埋入式柱脚应验算在轴力和弯矩作用下基础混凝土的侧向抗弯极限承载力,埋入式柱脚的极限受弯承载力不应小于钢柱全塑性抗弯承载力;与极限受弯承载力对应的剪力不应大于钢柱的全塑性抗剪承载力。
埋入式柱脚的计算,可按以下假设进行:钢柱的轴心压力N是由埋入的钢柱底板直接传递到钢筋混凝土基础上;柱脚处的弯矩M由埋入钢柱的翼缘与混凝土基础的承压力来传递给基础,或者由埋入部分钢柱上的抗剪焊钉来传递;柱脚的剪力v由埋入钢柱的翼缘和基础混凝土的承压力来传递。
采用钢管柱时埋入式柱脚的构造要求,截面宽厚比或径厚比较大(≥33)的箱形柱和钢管柱,其埋入部分应采取措施防止在混凝土侧压力下被压坏。常用方法是填充混凝土,填充高度应稍高于混凝土基础上表面;或在基础上端附近设置内隔板或外隔板。隔板的厚度应按计算确定,外隔板的外伸长度不应小于柱边长(或管径)1/10。对于有抗拔要求的埋入式柱脚,可在埋入部分设置栓钉。
钢柱边(角)柱柱脚埋入混凝土基础部分的上、下部位均需布置u形钢筋加强。当边(角)柱混凝土保护层厚度较小时,可能出现冲切破坏,可用下列方法之一补强:
设置栓钉。根据过去的研究,栓钉对于传递弯矩和剪力没有什么支配作用,但对于抗拉,由于栓钉受剪,能传递内力。
锚栓。因柱子的弯矩和剪力是靠混凝土的承压力传递的,当埋深较深时,在锚栓中几乎不引起内力,但柱受拉时,锚栓对传递内力起支配作用。在埋深较浅的柱脚中,加大埋深,提高底板和锚栓的刚度,可对锚栓传力起积极作用。
3.外包式柱脚抗震设计
外包式柱脚的特点,是钢柱底板与外包混凝土底部齐平,外包混凝土配有主筋和箍筋,顶部箍筋要集中配置,钢柱的外包部分要设置栓钉,钢柱翼缘外侧的混凝土保护层厚度一般不应小于150mm,外包式柱脚的内力分布进行设计。当钢柱与基础铰接时,柱脚弯矩完全由外包钢筋混凝土承受,柱的剪力也由外包混凝土承担。至于柱的轴力,一般认为,轴力可由钢柱底板直接传给基础,轴向拉力可通过底板的伸出边缘和锚栓传给基础。
外包式柱脚设计应注意的主要问题是:(1)当外包层高度较低时,外包层和柱面间很容易出现粘结破坏,为了确保刚度和承载力,外包层应达到柱截面的倍以上,其厚度应符合有效截面要求。(2)若主筋的粘结力和锚固长度不够,主筋在屈服前会拔出,使承载力降低。为此,主筋顶部一定要设弯钩,下端也应设弯钩并确保锚固长度不小于25d。(3)如果箍筋太少,外包层就会出现斜裂缝,箍筋至少要满足通常钢筋混凝土柱的设计要求,其直径和间距应符合规范规定。为了防止出现承压裂缝,使剪力能从主筋顺畅地传给钢筋混凝土,除了通常的箍筋外,柱顶密集配置几道箍筋十分重要。(4)抗震设计时,在柱脚达到最大受弯承载力之前,不应出现剪切裂缝。(5)采用箱形柱或圆管柱时,若壁板或管壁局部变形,承压力会集中出现在局部。为了防止局部变形,柱壁板宽厚比和径厚比应符合《钢结构设计规范》GB50017-2003关于塑性设计规定,也可在柱脚部分在钢管内浇灌注混凝土。
埋入式柱脚和外包式柱脚的混凝土保护层厚度均不小于180mm,钢柱埋人部分和外包部分均宜在柱翼缘上设置圆头焊钉,其直径不得小于16mm,其水平向和竖向的中心距离不得大于200mm。
4.结语
外包式和埋人式柱脚在抗震设计中已经被广泛应用,文章从受力等多方面对其具体设计进行了初步探讨,希望能为相关设计提供参考。
我是11年毕业生,和你论文一样的,现在奥鹏的论文题目会一样吗?下面是我准备的资料,免费给你,希望可以帮到你。以某一金工车间的梯形钢屋架为例,对其部分杆件进行计算。查阅相关资料,对钢结构的应用前景进行阐述,在钢结构的设计和使用中,建筑钢结构防腐仍是钢结构应用的主要难题。改善钢结构的防腐性能将对钢结构的发展和应用产生深远的影响。1、整理设计资料。2、根据设计资料进行相关的计算。3、阐述钢结构的应用前景。4、结合某一工程实例,阐述影响其耐久的主要问题以及提高钢结构耐腐蚀、耐火等耐久性的主要措施,
1、论文题目:要求准确、简练、醒目、新颖。2、目录:目录是论文中主要段落的简表。(短篇论文不必列目录)3、提要:是文章主要内容的摘录,要求短、精、完整。字数少可几十字,多不超过三百字为宜。4、关键词或主题词:关键词是从论文的题名、提要和正文中选取出来的,是对表述论文的中心内容有实质意义的词汇。关键词是用作机系统标引论文内容特征的词语,便于信息系统汇集,以供读者检索。 每篇论文一般选取3-8个词汇作为关键词,另起一行,排在“提要”的左下方。主题词是经过规范化的词,在确定主题词时,要对论文进行主题,依照标引和组配规则转换成主题词表中的规范词语。5、论文正文:(1)引言:引言又称前言、序言和导言,用在论文的开头。 引言一般要概括地写出作者意图,说明选题的目的和意义, 并指出论文写作的范围。引言要短小精悍、紧扣主题。〈2)论文正文:正文是论文的主体,正文应包括论点、论据、 论证过程和结论。主体部分包括以下内容:a.提出-论点;b.分析问题-论据和论证;c.解决问题-论证与步骤;d.结论。6、一篇论文的参考文献是将论文在和写作中可参考或引证的主要文献资料,列于论文的末尾。参考文献应另起一页,标注方式按《GB7714-87文后参考文献著录规则》进行。中文:标题--作者--出版物信息(版地、版者、版期):作者--标题--出版物信息所列参考文献的要求是:(1)所列参考文献应是正式出版物,以便读者考证。(2)所列举的参考文献要标明序号、著作或文章的标题、作者、出版物信息。
建筑工程的可以用
注浆技术在控制井筒涌水中的应用利用送压设备将能够固化的浆液材料通过钻孔注入地层中颗粒的间隙、土层的界面或岩层裂隙内,使其扩张、胶结、固化,以降低地层的渗透性,增强地层强度,防止地基沉降、变形的的注浆技术在控制井筒涌水中得到越来越广泛的应运。本文从注浆技术在控制井筒涌水中的原理出发,介绍了注浆技术在控制井筒涌水中的施工方案、方法及施工工艺,并对该技术在应用中的有关问题进行了探讨,得出注浆技术应用的在井筒涌水中优势。关键词:注浆技术 井筒涌水 应用 效果注浆技术的多层次应用在施工中已经使用普遍,具体在控制井筒涌水方面的优势已明显可现,以钱营孜煤矿副井为例 ,我们能更科学全面的认识注浆技术在控制井筒涌水中的应用,更好的利用。钱营孜煤矿副井井筒设计净直径,井深708m,其中表土段264m,采用冻结法施工;基岩段444m采用地面预注浆法施工。表土段内壁已于2007年4月11日套壁完毕(表土段停冻时间为4月2日),现井筒施工至井深,井筒淋水量约17m3/h左右。为保证施工安全和改善井下工作面施工条件,于2007年10月15日暂停井筒掘砌施工转为基岩段壁后注浆和表土段壁间注浆。二、施工工艺1、造浆站布置与注浆站布置利用井口设置Js-1000型砼搅拌机拌制浆液,制造浆液时浆液必须搅拌均匀,吊桶接浆下送,接浆时吊桶上口设过滤筛,下至井下二层吊盘,吊桶内设扫孔器一个,继续搅拌灰浆以防沉淀;水玻璃用4个塑料桶通过吊桶送至下吊盘。注浆站设置在二层吊盘上,布置注浆泵一台,凿岩机一台,浆桶三个,及相应的各种管路(泵与孔口上混合器用高压胶管连接)、电缆、电器设备、信号及通讯设施等。注意设备摆设要保持吊盘重心不偏移。2、注浆流程为: 搅拌 贮浆桶 注浆泵 混合器 注浆管 含水层3、注浆顺序:自下而上,再由上往下往复注浆,但在最低出水层位下,应先注浆封堵水路。4、注浆结束标准注浆结束标准以注浆压力升至设计终压,且孔内不吸浆,出水点不再出水,10分钟打开孔口管放浆阀,不漏水,井壁不见出水点,全井筒涌水量不超过6m3/h,可结束本次注浆。三、注浆参数:1、注浆压力基岩段注浆最大压力不得大于7Mpa。水力冲孔瞬时压力不超过8Mpa。表土段夹层注浆内壁砼强度C30的,注浆压力不大于5Mpa;内壁砼强度C30以上的,注浆压力不大于7Mpa。2、布孔①表土段:井深(绝对标高)-15m、、设计水平,环向均匀布置6个注浆孔。②表土段壁座下方-239m(累深264m)处单独施工一排注浆孔。③基岩段:以出水点为主,注浆段高不大于50m,环向均匀布置6个注浆孔,对于主要出水点则采用顶水对点布孔或在周围布孔。④基岩段打眼后,若无水则用水泥药卷封堵严实,表土段则将注浆管砸入井壁并加盖预留。⑤打眼用7655型风钻配Ф42钻头,孔口管采用Ф40×500mm的无缝钢管加工成马牙扣型,尾部焊挡板及1寸丝头,孔口管外壁用麻丝反复缠绕后,然后用大锤将带有保护管丝的孔口管撞入孔内,注浆管外露不超过50mm,装上注浆阀门后,连通注浆管路,进行清水试压。3、孔深:基岩段以超过井壁厚度100mm、表土段以穿透内壁且进入外壁不超过50mm为原则。4、浆液浓度水泥浆的水灰比为1:1、:1,(见浆液配比对照表),水泥与水玻璃体积比为1:1、1:。注浆时原则上用单液水泥浆,若井壁跑浆,则用双液浆封堵,间歇式注浆或用棉纱、铁楔先堵水眼后再注。浆液配比对照表水灰比水(kg)水 泥(kg)浆 量(m3)1:四、施工安全技术1、基岩段打眼时,如发现涌水较大或涌水中含砂时,停止钻进,立即注浆。2、冻结段打眼时,在即将穿透内壁时停一下,观察无异常时再进行钻进。3、打眼时,操作人员两侧站立,不得站在风钻后面,以防顶钻伤人。严格交接班制度,交接班时井下情况要交代清楚。4、吸浆笼头应加过滤罩,以避免笼头堵死,笼头工要密切注意吸浆情况,发现异常,及时处理。5、每孔注浆完毕后必须用水泥封闭严实,封孔工作一定要认真,要经跟班队长和技术员检查合格后方可结束;打眼所产生的盲孔都要用水泥掺水玻璃封堵。6、注浆时要安排专人要观察注浆压力和井壁情况,以防井壁破裂,随时观察有无漏浆现象及位置,并及时采取处理措施。7、若井壁漏浆严重,可以调节浆液凝固时间或采取点注方法;8、压力表必须安装在水玻璃的管路上,发现压力表失灵及时更换。9、注浆人员要尽量远离注浆孔,开阀门人员要站在混合器两侧。10、注浆结束以后要立即对设备和管路进行全面清洗,注浆孔口管外露部分割除。五、注浆效果1、在注浆前后对井筒进行测水并做好记录,作为本次注浆效果检验依据。2、本次注浆共注入水泥水泥,水玻璃,三乙醇胺千克,食盐千克。3、10月25日经建设单位和监理单位共同测水为井筒涌水,表明注浆效果良好。通过注浆结束后的观察,井筒淋水无异常变化,原来各出水点均无出现渗水现象。因此,本次注浆对封堵井筒涌水起到了较好的效果,是一种切实可行的堵水方法,是符合中国国情的一种可行的控制井筒涌水方法,注浆技术在控制井筒涌水产生理想效果,必会产生良好的经济效益和社会效益。
建筑工程中深基坑降水技术的研究摘 要:介绍了井管井点降水的施工特点,结合实际工程,阐述了井管井点降水技术在建筑工程深基坑中的应用,阐述了基坑降水的设计、施工流程。关键词:建筑、深基坑、井管井点降水这个就是属于建筑技术的论文,不知LZ觉得怎么样,如果行的话就支持 鲁文建筑论文 吧,我是在那里找到的,呵呵还有很多关于建筑技术的论文谈梁高空膺架制梁工法 探讨预应力CFRP加固钢结构技 建筑物不均匀沉降处理方法研究 论雷电防护技术在建筑中的应用与 论钢结构在民用建筑的应用 建筑工程中深基坑降水技术的研究 论钢筋混凝土裂缝的形态及补救措 关于工民建中防渗漏技术的研究 浅析钢结构住宅的设计原则及发展 不规则建筑结构地震反应分析与性 混凝土裂缝成因分析与防治处理 探讨农村建房的抗震措施 一种建筑施工技术知识表示方式的 浅谈我国高层钢结构建筑的发展及 关于建筑施工技术控制的问题探讨 地震中建筑工程质量缺陷的民事责 逆作法施工技术在建筑工程的应用 建筑工程技术专业建设探讨 谈先张法预应力空心板梁的施工技